Delta DOP-300S DOP-3S07S3E2 7-inch IIoT Touch HMI

DOP-3S07S3E2 is a Delta DOP-300S 7-inch touch hmi with 1024 × 600 pixel TFT LCD display. It operates on 24V DC and provides RS-232, RS-422, RS-485; Ethernet × 2; USB Host Type-A × 1, Type-C × 1. Project configuration uses DIAScreen. Suitable for operator visualization with compatible external controllers.

ModelDOP-3S07S3E2
Warranty12 Months

Original price was: 18,000.00৳ .Current price is: 16,500.00৳ .

Price (incl. VAT)

BrandDelta
SeriesDOP-300S
ModelDOP-3S07S3E2
Part NoDOP-3S07S3E2
HMI TypeTouch HMI
Display Size7″
Display Resolution1024 × 600 px
Display TechnologyTFT LCD
Input TypeResistive touch
Program Memory512 MB
Memory Card SupportYes
Programming SoftwareDIAScreen
Communication PortsEthernet, RS-232, RS-422, RS-485, USB Type-A, USB Type-C
Built-in Communication ProtocolsEtherNet/IP, Modbus, MQTT, OPC UA
PLC CompatibilityDelta Controllers, Protocol/Driver-Dependent
Power Supply24V DC
Dimensions (W × H × D)196 × 136 × 39 mm
Panel Cutout Dimensions186.8 × 126.8 mm
Product Weight880 g
Mounting OrientationLandscape
Protection RatingIP66, NEMA 4, UL Type 4X (Front)
Warranty12 Months

Delta DOP-300S DOP-3S07S3E2 7-inch IIoT Touch HMI

DOP-3S07S3E2 is the 7 inch DOP-300S operator panel identified in this listing. Its purpose is to let personnel inspect machine status, enter setpoints, acknowledge operator messages and interact with a correctly configured industrial control system. It is an HMI interface, not a standalone PLC or an industrial panel computer. The selected order code is important: a display size, communication connector or hardware suffix from another Delta model must not be used as a substitute when preparing a project, purchasing a replacement, or machining an enclosure.

Display and Operator Interface

The 7 inch TFT LCD screen has native resolution 1024 × 600 pixels. Native resolution describes the HMI’s own display rather than a monitor connected through an external interface. Operator entry uses resistive touch, which is suitable for on-screen buttons, menus and numerical entries created in a compatible project. Display elements should be sized for the actual panel and tested using the selected model in the editor. A different screen diagonal or pixel matrix can change text layout and control positioning even within one product family.

Communication and PLC Compatibility

Physical interfaces documented for this listing are RS-232, RS-422, RS-485; Ethernet × 2; USB Host Type-A × 1, Type-C × 1. Physical ports must not be confused with installed communication drivers or active protocols. The specification value for protocols is MQTT, OPC UA, Modbus, EtherNet/IP, and controller compatibility is recorded as Delta controllers; protocol/driver-dependent. Delta publishes MQTT, OPC UA, Modbus and EtherNet/IP among its DOP-300S communication capabilities; actual connections require the appropriate software project, addressing and network configuration. Network connectivity does not automatically enable cloud services, remote viewing or third-party protocols.

Programming and Runtime Functions

HMI projects are prepared using DIAScreen. A project should begin with the exact device selection and its actual communication settings, followed by screen objects, navigation, messages and the appropriate controller addresses. DOP-300S is positioned for connected industrial monitoring, but cloud onboarding, remote access and any service account or licence conditions must be assessed separately. Never treat a network connector as proof that a particular remote protocol is active.

Memory and Storage

The displayed Program Memory field is 512 MB. For this HMI it reflects documented total internal Flash ROM capacity; it is not a separate verification of how much space is available to the user project. Memory-card support is listed as Yes (microSD). Removable media is a supported interface but a memory card is not assumed to be supplied with the panel. Runtime records and historical data should be planned against the actual firmware functions and available storage.

Installation and Typical Applications

The rated power entry is 24V DC. The reported external dimensions are 196 × 136 × 39 mm (width × height × depth). The listed panel opening is 186.8 × 126.8 mm (width × height). Protection is recorded as IP66 / NEMA 4 / UL Type 4X (Front); this should not be interpreted as proof that every exposed connector or rear surface has the same ingress rating. Use the specified fasteners, grounding and panel gasket conditions in the installation guide. Before manufacturing the cabinet, verify the drawing revision, mounting thickness, ventilation clearance and cable bend radius.

Exact Variant Verification

This entry identifies the IIoT variant, not every product in DOP-300S. The installed model number should match DOP-3S07S3E2 exactly. The 7-inch and 10.1-inch DOP-300S units use the same general communication architecture but have different chassis dimensions, cutouts and product weights. If an identified feature is not verified in the source notes, leave it open rather than copying a specification from a similarly named device.

Engineering Integration Checklist

For commissioning, first confirm the unit’s actual nameplate and hardware revision. Prepare a supported power supply and grounding scheme, and verify the display orientation and clearance against the correct mechanical drawing. In the HMI project, choose the device and communication driver deliberately, confirm baud rate or IP addressing, and test reading and writing one safe controller tag before connecting wider machine functions. Store a backup of the accepted project and record the firmware and editor versions. Operator controls should be designed as part of the wider machine safeguarding strategy; an ordinary HMI touch button does not replace a certified emergency-stop circuit or a safety controller.

Official Manufacturer Links

Official Manufacturer Product Page Link:
Official Manufacturer Datasheet / Technical Documentation Link:

Similar Products:

DOP-300S Series HMI

• 7 in TFT LCD, 1024 × 600 px
• Resistive Touch operator entry
• 24V DC rated supply
• RS-232, RS-422, RS-485; Ethernet × 2; USB Host Type-A × 1, Type-C × 1
• HMI software: DIAScreen
• Yes (microSD) memory-card support
• IP66 / NEMA 4 / UL Type 4X (Front)
• DIACloud-capable IIoT platform (activation/service conditions apply)

Reviews

There are no reviews yet.

Be the first to review “Delta DOP-300S DOP-3S07S3E2 7-inch IIoT Touch HMI”

Your email address will not be published. Required fields are marked *

• Industrial IoT data collection and visualization
• Pump and compressor station monitoring
• Local HMI operator station for PLC systems
• Ethernet-connected equipment dashboards
• Factory machine status and alarm visualization
• Connected production-line monitoring with configured cloud access

This is shipping and returns content

Need Help Choosing?

Our automation experts are ready to help you select the right product for your application.

  • Application Consultation
  • Product Selection Support
  • Wiring & Integration Help
  • After Sales Support
Chat on WhatsApp

+880 1553-346553